DG SET SUPPLY SCOPE WITH MANUAL CONTROL PANEL
ENGINE: | "CUMMINS" standard design, water cooled diesel engine turbocharged, 1500 RPM, complete with: | |
Flywheel with Ring Coupling Air Cleaner Corrosion Resistor Radiator with fan/heat exchanger PT Fuel PumpEFC/PSG Hydraulic Governor Fuel Filter Safety Control (trip) for |
Lube Oil Filter Lube Oil Bypass Filter Exhaust Silencer 24V DC Starter Battery Charging Dynamo Water Seperater Battery Charging Dynamo - Low Lube Oil Pressure - High Water Temperature - Over Speed (Optional Extra) |
|
ALTERNATOR: | Brushiess, suitable rated at 0.8PF, 415V, 3 Phase, 4 wires, 50 cycles per sec., 1500 RPM, self excited and self regulated with brushiess excitation, Band of Voltage + 2.5% of rated voltage from no load to full load, Class F Insulation conforming to BS: 2613/IS: 4722 | |
SKID: | Specially designed channel iron Base Frame fabricated, welded construction to accomodate Engine and Alternator with bottom drilled holes for solid foundation or Anti-Vibration Mounts. | |
CONTROL PANEL: | Sheet steel cubicle, front or back access, bottom cable entry, Manual Switching Panel, incorporating MCCB or ACB, Voltmeter with Selector Switch, Arnmeter with Selector Switch, KW Meter, PF Meter, KWH Meter, Announciation. (Refer Specification Sheet for more details). | |
FULE TANK: | 250/500/750/990 litres capacity depending on rating of Set, floor mounted complete with Fuel Level Indicator Fuel Inlet and Outlet, Air vent, drain, plug inlet arrangement for direct filling and set of 5ft.long Braided fuel hoses. | |
BATTERY: | 2/4 x 12 Volts dry, unchanged batteries with connecting leads and terminals. | |
DOCUMENTS: | Engine Manual, Spare
Parts Book, Warranty Certificate, Control Panel Schematic drawing, Alternator Manual and
Test Certificates. DIESEL GENERATING SETS
FOR SPEOML APPLICATIONS: |
CUMMINS RATING TABLE
POWERICA
MODEL |
ENGINE TYPE |
RATING AT 50 HZ, 1500 RPM, 0.8PF |
INFORMATION |
||||
CONTINUOUS |
STANDBY |
BHP |
CYLS |
||||
65 PCU |
N-495 -G1 |
KW |
KVA |
KW |
KVA |
||
80 PCU |
N-495 - G |
52 |
65 |
57 |
72 |
81 |
4 |
100 PCU |
NT-495 - G |
64 |
80 |
70 |
88 |
92 |
4 |
125 PCU |
NTC-495 -G |
80 |
100 |
88 |
110 |
127 |
4 |
140 PCU |
NTA-495 -G |
100 |
125 |
110 |
138 |
154 |
4 |
160 PCU |
NT-743 -G1 |
112 |
140 |
123 |
154 |
173 |
6 |
180 PCU |
NT-743 - G |
128 |
160 |
140 |
176 |
205 |
6 |
200 PCU |
NTA-743 -G |
144 |
180 |
158 |
198 |
231 |
6 |
250 PCU |
NTA-855 -G |
160 |
200 |
176 |
220 |
255 |
6 |
285 PCU |
NTA-855-G2 |
200 |
250 |
220 |
275 |
306 |
6 |
DERATION
NIL UPTO 38 DEG. C, 5000
FT ASL, 80% RH
OVERLOAD-
10% FOR ONE HOUR
DURING 12 HOURS
CONTINIOUS OPERATION
ASPIRATION
N-NATURALLY ASPIRATED
T-TURBOCHARGED (TC),
TA-TC AFTER COLLED,
TC COUNTER BALANCE
SHIPPING DIMENSIONS [UNPACKED] OF BASIC SETS
POWERICA DG SET MODEL |
DG SET DIMENSIONS [APPROX]. |
GROSS WEIGHT |
||
L [MM] |
W [MM] |
H [MM] |
[KGS.] |
|
65 PCU |
2600 |
1050 |
1350 |
2400 |
80 PCU |
2600 |
1050 |
1350 |
2400 |
100 PCU |
2800 |
1050 |
1350 |
2600 |
125 PCU |
2800 |
1050 |
1400 |
2700 |
140 PCU |
2800 |
1050 |
1400 |
3000 |
160 PCU |
3500 |
1050 |
1550 |
3400 |
180 PCU |
3500 |
1050 |
1550 |
3400 |
200 PCU |
3500 |
1050 |
1550 |
3600 |
250 PCU |
3600 |
1200 |
1650 |
3700 |
285 PCU |
3700 |
1200 |
1650 |
3700 |